R-134a PT Chart

Quick Answer

At 40 °F, R-134a is at 35.0 psig at sea level. Set your elevation in the lookup if you are well above sea level.

R-134a pressure and temperature

35.0psig

R-134a at 40 °F, sea level

Gauge pressure assumes sea-level air (14.7 psia). Set your elevation if you are well above sea level: a gauge reads against the air around it.

R-134a pressure-temperature chart · GreenCalculus · greencalculus.com/data/r-134a-pt-chart/

Gauge pressure at sea level, -40 to 150 °F. Below 0 psig the reading is a vacuum, in inches of mercury.

Temp (°F)Pressure (psig)
-4014.8 inHg vac
-3914.4 inHg vac
-3813.9 inHg vac
-3713.4 inHg vac
-3613.0 inHg vac
-3512.5 inHg vac
-3412.0 inHg vac
-3311.4 inHg vac
-3210.9 inHg vac
-3110.4 inHg vac
-309.8 inHg vac
-299.3 inHg vac
-288.7 inHg vac
-278.1 inHg vac
-267.5 inHg vac
-256.9 inHg vac
-246.3 inHg vac
-235.7 inHg vac
-225.0 inHg vac
-214.3 inHg vac
-203.7 inHg vac
-193.0 inHg vac
-182.3 inHg vac
-171.5 inHg vac
-160.8 inHg vac
-150.1 inHg vac
-140.4
-130.7
-121.1
-111.5
-101.9
-92.4
-82.8
-73.2
-63.6
-54.1
-44.6
-35.0
-25.5
-16.0
06.5
17.0
27.5
38.0
48.5
59.1
69.6
710.2
810.8
911.3
1011.9
1112.5
1213.1
1313.8
1414.4
1515.0
1615.7
1716.4
1817.0
1917.7
2018.4
2119.1
2219.9
2320.6
2421.3
2522.1
2622.9
2723.7
2824.5
2925.3
3026.1
3126.9
3227.8
3328.6
3429.5
3530.4
3631.3
3732.2
3833.1
3934.1
4035.0
4136.0
4237.0
4338.0
4439.0
4540.1
4641.1
4742.2
4843.2
4944.3
5045.4
5146.6
5247.7
5348.9
5450.0
5551.2
5652.4
5753.6
5854.9
5956.1
6057.4
6158.7
6260.0
6361.3
6462.7
6564.0
6665.4
6766.8
6868.2
6969.7
7071.1
7172.6
7274.1
7375.6
7477.1
7578.7
7680.2
7781.8
7883.4
7985.0
8086.7
8188.4
8290.0
8391.8
8493.5
8595.2
8697.0
8798.8
88100.6
89102.5
90104.3
91106.2
92108.1
93110.0
94112.0
95113.9
96115.9
97118.0
98120.0
99122.1
100124.2
101126.3
102128.4
103130.6
104132.7
105135.0
106137.2
107139.5
108141.7
109144.0
110146.4
111148.7
112151.1
113153.5
114156.0
115158.4
116160.9
117163.4
118166.0
119168.6
120171.2
121173.8
122176.5
123179.1
124181.8
125184.6
126187.4
127190.1
128193.0
129195.8
130198.7
131201.6
132204.6
133207.5
134210.6
135213.6
136216.7
137219.7
138222.9
139226.0
140229.2
141232.4
142235.7
143239.0
144242.3
145245.7
146249.0
147252.5
148255.9
149259.4
150262.9
SourceCoolProp 8.0.0, reference equation of state
Range-40 to 150 °F, -40 to 65 °C
Checked againstNIST, Arkema
LicenceCC BY 4.0

R-134a is the HFC that replaced R-12 in car air-conditioning, and Chemours sells it as an automotive refrigerant. This chart gives its saturation pressure at every whole degree from -40 to 150 °F, computed from the reference equation of state and checked against NIST and Arkema.

Checked

We compared every value with 3 published tables from NIST and Arkema. They agree with this chart to within 0.08 psi at every temperature both cover. How we checked

How to read an R-134a PT chart

A pressure-temperature (PT) chart gives the pressure at which a refrigerant boils or condenses at each temperature: its saturation pressure. Where liquid and vapor are both present, as in an evaporator, a condenser or a cylinder, the pressure and the temperature are tied together, so a gauge reading tells you the temperature the refrigerant is boiling or condensing at.

The pressures are gauge pressure (psig) at sea level. Below 0 psig the refrigerant is under vacuum, and the chart shows inches of mercury instead. Switch the units above to °C, kPa or bar, and type any temperature or pressure into the lookup for a value between the rows.

Superheat and subcooling: a worked example

The lookup above does both calculations. Here is what it does, with example readings. They show the method only; they are not target pressures for any system.

Worked example

Superheat. The suction gauge reads 35 psig and the suction line is at 52 °F. On the saturation line, 35 psig is a saturation temperature of 40.0 °F. Superheat is 52 − 40.0 = 12.0 °F.

Subcooling. The liquid line gauge reads 124 psig and the liquid line is at 90 °F. On the saturation line, 124 psig is 99.9 °F. Subcooling is 99.9 − 90 = 9.9 °F.

Whether a superheat or subcooling figure is right for a system depends on that system. Compare with the manufacturer’s charging instructions.

How far off a reading can be

Superheat and subcooling are differences of a few degrees, so a small error in the pressure shows up in the answer. This table works out, from the R-134a chart itself, how far each common mistake moves the result.

MistakeSuperheat
suction at 40 °F
Subcooling
liquid at 100 °F
The gauge reads 1 psi offoff by 1.0 °F (0.6 °C)off by 0.5 °F (0.3 °C)
At 5,000 ft, using a sea-level chartreads high by 2.6 °F (1.4 °C)reads low by 1.2 °F (0.7 °C)

Worked out from this chart. For R-134a, 1 °F is about 1.0 psi at a 40 °F suction and 2.1 psi at a 100 °F liquid line. At 5,000 ft a gauge reads 2.5 psi lower than at sea level for the same refrigerant pressure. R-134a is a single compound, so it has one column and no column mix-up.

Gauge pressure and elevation

A gauge reads the difference between the refrigerant’s pressure and the air around it. Air pressure falls with height, so at the same temperature a gauge reads higher up a mountain than at sea level. At 40 °F, R-134a reads 35.0 psig at sea level and 37.5 psig at 5,000 ft, where standard air pressure is 12.23 psia.

Enter your elevation in the lookup and the whole chart, CSV and printout switch to it. The tool uses the standard atmosphere, which is what Arkema’s 5,000 ft chart uses; our values match that chart to within 0.08 psi. Weather moves air pressure too, by much less.

About R-134a

GreenCalculus MasterBrain data version 2026.284 · 1 factor from IPCC AR6 · key refrigerants.r_134a · each resolves at verify.greencalculus.com/‹key› with its source cell.
TypeHFC, single compound
CompositionSingle compound, 1,1,1,2-tetrafluoroethane (CH2FCF3)
ASHRAE 34 safety classA1: lower toxicity, no flame propagation
GWP-100 (IPCC AR6)1530
Boiling point at 1 atm
-14.9 °F (-26.1 °C)
Critical temperature
213.9 °F (101.1 °C)
Critical pressure
588.7 psia (4,059 kPa)

Boiling point and critical point are computed from the same equation of state as the chart. GWP is from our refrigerant GWP dataset; the refrigerant leakage calculator turns a leak into CO2e.

Chemours describes R-134a as a non-ozone-depleting HFC that replaced R-12 and as the standard for mobile air-conditioning (Chemours). A car’s air-conditioning pressures depend on engine speed, airflow and the system, and a saturation table is not a charging target. Follow the vehicle maker’s service information.

How we checked these numbers

Every value is computed with CoolProp 8.0.0 from the reference equation of state for R-134a (Tillner-Roth and Baehr (1994), Journal of Physical and Chemical Reference Data 23(5)), as absolute pressure, then converted to gauge. Before publishing, we compared it with every independent table we could find:

Published tableLargest gapPoints comparedRange
NIST Chemistry WebBook, saturation properties (SRD 69)0.00 psi at 136 °F190-40 to 150 °F
Arkema, Forane refrigerant pressure-temperature chart, PPC/SDC 05-2025 (NIST REFPROP 10)0.05 psi at 95 °F39-40 to 150 °F
Arkema, Forane pressure-temperature chart, high elevation (5,000 ft) (NIST REFPROP 9) (at 5,000 ft)0.08 psi at 60 °F35-20 to 150 °F

Gauge pressure at 5,000 ft: our absolute pressure less standard-atmosphere air pressure there (12.23 psia).

Checked 28 Oct 2026. A chart printed to one decimal place rounds by up to 0.05 psi.

The °C table is computed at whole degrees Celsius, not converted from the °F rows, and the two agree to within 0.01 psi.

Questions about the R-134a PT chart

At sea level, R-134a is at 35.0 psig at 40 °F. At 5,000 ft the same refrigerant reads 37.5 psig, because the gauge reads against thinner air.

The chart gives the saturation pressure at each temperature, not an operating target. Running pressures depend on the system, the load, the airflow and the charge. Compare with the manufacturer’s charging instructions, and use the chart to turn a gauge reading into a saturation temperature for superheat or subcooling.

When a system has been off long enough to even out, any part holding both liquid and vapor sits at the saturation pressure for its temperature. At 70 °F that is 71.1 psig for R-134a at sea level. It shows refrigerant is present, not how much.

Yes. A gauge reads against the air around it, and air pressure falls with height. At 5,000 ft the standard atmosphere is 12.23 psia instead of 14.70, so every gauge reading is about 2.5 psi higher than at sea level for the same refrigerant temperature. Set your elevation in the lookup to correct the whole chart.

Not on its own. The chart gives the pressure at which R-134a boils at each temperature, which is useful for reading a gauge, but a car system’s pressures depend on engine speed, airflow and the system itself. Follow the vehicle maker’s service information.

Other refrigerants

Pressures are gauge at sea level; for blends, liquid (bubble) / vapor (dew). Safety classes are ASHRAE 34.

Version history

  • 1.1.1 (29 October 2026): sources moved into a compact card at the end of the page, so they no longer break up the reading.
  • 1.1 (28 October 2026): new section on how far off a reading can be, worked out for this refrigerant, and a note on how closely the published charts agree.
  • 1.0.1 (28 October 2026): other refrigerants shown as cards, with each gas’s use, pressure at 40 °F, type and safety class.
  • 1.0 (28 October 2026): first published.
Scroll to Top