R-290 PT Chart
At 40 °F, R-290 is at 63.9 psig at sea level. Set your elevation in the lookup if you are well above sea level.
R-290 pressure and temperature
R-290 at 40 °F, sea level
Gauge pressure assumes sea-level air (14.7 psia). Set your elevation if you are well above sea level: a gauge reads against the air around it.
R-290 pressure-temperature chart · GreenCalculus · greencalculus.com/data/r-290-pt-chart/
Gauge pressure at sea level, -40 to 150 °F. Below 0 psig the reading is a vacuum, in inches of mercury.
| Temp (°F) | Pressure (psig) |
|---|---|
| -40 | 1.4 |
| -39 | 1.8 |
| -38 | 2.2 |
| -37 | 2.6 |
| -36 | 3.0 |
| -35 | 3.4 |
| -34 | 3.9 |
| -33 | 4.3 |
| -32 | 4.8 |
| -31 | 5.2 |
| -30 | 5.7 |
| -29 | 6.1 |
| -28 | 6.6 |
| -27 | 7.1 |
| -26 | 7.6 |
| -25 | 8.1 |
| -24 | 8.6 |
| -23 | 9.1 |
| -22 | 9.6 |
| -21 | 10.2 |
| -20 | 10.7 |
| -19 | 11.3 |
| -18 | 11.8 |
| -17 | 12.4 |
| -16 | 13.0 |
| -15 | 13.6 |
| -14 | 14.2 |
| -13 | 14.8 |
| -12 | 15.4 |
| -11 | 16.1 |
| -10 | 16.7 |
| -9 | 17.4 |
| -8 | 18.0 |
| -7 | 18.7 |
| -6 | 19.4 |
| -5 | 20.1 |
| -4 | 20.8 |
| -3 | 21.5 |
| -2 | 22.2 |
| -1 | 22.9 |
| 0 | 23.7 |
| 1 | 24.5 |
| 2 | 25.2 |
| 3 | 26.0 |
| 4 | 26.8 |
| 5 | 27.6 |
| 6 | 28.4 |
| 7 | 29.2 |
| 8 | 30.1 |
| 9 | 30.9 |
| 10 | 31.8 |
| 11 | 32.7 |
| 12 | 33.6 |
| 13 | 34.5 |
| 14 | 35.4 |
| 15 | 36.3 |
| 16 | 37.2 |
| 17 | 38.2 |
| 18 | 39.2 |
| 19 | 40.1 |
| 20 | 41.1 |
| 21 | 42.1 |
| 22 | 43.2 |
| 23 | 44.2 |
| 24 | 45.2 |
| 25 | 46.3 |
| 26 | 47.4 |
| 27 | 48.5 |
| 28 | 49.6 |
| 29 | 50.7 |
| 30 | 51.8 |
| 31 | 53.0 |
| 32 | 54.1 |
| 33 | 55.3 |
| 34 | 56.5 |
| 35 | 57.7 |
| 36 | 58.9 |
| 37 | 60.1 |
| 38 | 61.4 |
| 39 | 62.7 |
| 40 | 63.9 |
| 41 | 65.2 |
| 42 | 66.5 |
| 43 | 67.9 |
| 44 | 69.2 |
| 45 | 70.6 |
| 46 | 72.0 |
| 47 | 73.4 |
| 48 | 74.8 |
| 49 | 76.2 |
| 50 | 77.6 |
| 51 | 79.1 |
| 52 | 80.6 |
| 53 | 82.1 |
| 54 | 83.6 |
| 55 | 85.1 |
| 56 | 86.7 |
| 57 | 88.2 |
| 58 | 89.8 |
| 59 | 91.4 |
| 60 | 93.0 |
| 61 | 94.7 |
| 62 | 96.3 |
| 63 | 98.0 |
| 64 | 99.7 |
| 65 | 101.4 |
| 66 | 103.1 |
| 67 | 104.9 |
| 68 | 106.6 |
| 69 | 108.4 |
| 70 | 110.2 |
| 71 | 112.0 |
| 72 | 113.9 |
| 73 | 115.7 |
| 74 | 117.6 |
| 75 | 119.5 |
| 76 | 121.4 |
| 77 | 123.4 |
| 78 | 125.4 |
| 79 | 127.3 |
| 80 | 129.3 |
| 81 | 131.4 |
| 82 | 133.4 |
| 83 | 135.5 |
| 84 | 137.6 |
| 85 | 139.7 |
| 86 | 141.8 |
| 87 | 143.9 |
| 88 | 146.1 |
| 89 | 148.3 |
| 90 | 150.5 |
| 91 | 152.8 |
| 92 | 155.0 |
| 93 | 157.3 |
| 94 | 159.6 |
| 95 | 161.9 |
| 96 | 164.3 |
| 97 | 166.7 |
| 98 | 169.1 |
| 99 | 171.5 |
| 100 | 173.9 |
| 101 | 176.4 |
| 102 | 178.9 |
| 103 | 181.4 |
| 104 | 183.9 |
| 105 | 186.5 |
| 106 | 189.1 |
| 107 | 191.7 |
| 108 | 194.3 |
| 109 | 197.0 |
| 110 | 199.6 |
| 111 | 202.4 |
| 112 | 205.1 |
| 113 | 207.8 |
| 114 | 210.6 |
| 115 | 213.4 |
| 116 | 216.3 |
| 117 | 219.1 |
| 118 | 222.0 |
| 119 | 224.9 |
| 120 | 227.8 |
| 121 | 230.8 |
| 122 | 233.8 |
| 123 | 236.8 |
| 124 | 239.9 |
| 125 | 242.9 |
| 126 | 246.0 |
| 127 | 249.1 |
| 128 | 252.3 |
| 129 | 255.5 |
| 130 | 258.7 |
| 131 | 261.9 |
| 132 | 265.2 |
| 133 | 268.5 |
| 134 | 271.8 |
| 135 | 275.1 |
| 136 | 278.5 |
| 137 | 281.9 |
| 138 | 285.4 |
| 139 | 288.8 |
| 140 | 292.3 |
| 141 | 295.8 |
| 142 | 299.4 |
| 143 | 303.0 |
| 144 | 306.6 |
| 145 | 310.2 |
| 146 | 313.9 |
| 147 | 317.6 |
| 148 | 321.4 |
| 149 | 325.1 |
| 150 | 328.9 |
R-290 is propane used as a refrigerant. This chart gives its saturation pressure at every whole degree from -40 to 150 °F, computed from the reference equation of state for propane and checked against NIST.
We compared every value with 1 published table from NIST. It agrees with this chart to within 0.01 psi at every temperature both cover, closer than a chart printed to one decimal place can show. How we checked
How to read an R-290 PT chart
A pressure-temperature (PT) chart gives the pressure at which a refrigerant boils or condenses at each temperature: its saturation pressure. Where liquid and vapor are both present, as in an evaporator, a condenser or a cylinder, the pressure and the temperature are tied together, so a gauge reading tells you the temperature the refrigerant is boiling or condensing at.
The pressures are gauge pressure (psig) at sea level. Below 0 psig the refrigerant is under vacuum, and the chart shows inches of mercury instead. Switch the units above to °C, kPa or bar, and type any temperature or pressure into the lookup for a value between the rows.
Superheat and subcooling: a worked example
The lookup above does both calculations. Here is what it does, with example readings. They show the method only; they are not target pressures for any system.
Superheat. The suction gauge reads 64 psig and the suction line is at 52 °F. On the saturation line, 64 psig is a saturation temperature of 40.0 °F. Superheat is 52 − 40.0 = 12.0 °F.
Subcooling. The liquid line gauge reads 174 psig and the liquid line is at 90 °F. On the saturation line, 174 psig is 100.0 °F. Subcooling is 100.0 − 90 = 10.0 °F.
Whether a superheat or subcooling figure is right for a system depends on that system. Compare with the manufacturer’s charging instructions.
How far off a reading can be
Superheat and subcooling are differences of a few degrees, so a small error in the pressure shows up in the answer. This table works out, from the R-290 chart itself, how far each common mistake moves the result.
| Mistake | Superheat suction at 40 °F | Subcooling liquid at 100 °F |
|---|---|---|
| The gauge reads 1 psi off | off by 0.8 °F (0.4 °C) | off by 0.4 °F (0.2 °C) |
| At 5,000 ft, using a sea-level chart | reads high by 1.9 °F (1.1 °C) | reads low by 1.0 °F (0.6 °C) |
Worked out from this chart. For R-290, 1 °F is about 1.3 psi at a 40 °F suction and 2.5 psi at a 100 °F liquid line. At 5,000 ft a gauge reads 2.5 psi lower than at sea level for the same refrigerant pressure. R-290 is a single compound, so it has one column and no column mix-up.
Gauge pressure and elevation
A gauge reads the difference between the refrigerant’s pressure and the air around it. Air pressure falls with height, so at the same temperature a gauge reads higher up a mountain than at sea level. At 40 °F, R-290 reads 63.9 psig at sea level and 66.4 psig at 5,000 ft, where standard air pressure is 12.23 psia.
Enter your elevation in the lookup and the whole chart, CSV and printout switch to it. The tool uses the standard atmosphere, the same basis as Arkema’s published 5,000 ft chart. Weather moves air pressure too, by much less.
About R-290
| Type | Hydrocarbon (propane) |
|---|---|
| Composition | Single compound, propane (CH3CH2CH3) |
| ASHRAE 34 safety class | A3: lower toxicity, higher flammability |
| GWP-100 (IPCC AR6) | 0.02 |
- Boiling point at 1 atm
- -43.8 °F (-42.1 °C)
- Critical temperature
- 206.1 °F (96.7 °C)
- Critical pressure
- 616.6 psia (4,251 kPa)
Boiling point and critical point are computed from the same equation of state as the chart. GWP is from our refrigerant GWP dataset; the refrigerant leakage calculator turns a leak into CO2e.
R-290 is classed A3, higher flammability. Work on R-290 equipment only with the training and tools the equipment maker specifies.
How we checked these numbers
Every value is computed with CoolProp 8.0.0 from the reference equation of state for R-290 (Lemmon, McLinden and Wagner (2009), Journal of Chemical and Engineering Data 54(12)), as absolute pressure, then converted to gauge. Before publishing, we compared it with every independent table we could find:
| Published table | Largest gap | Points compared | Range |
|---|---|---|---|
| NIST Chemistry WebBook, saturation properties (SRD 69) | 0.00 psi at 134 °F | 190 | -40 to 150 °F |
Checked 28 Oct 2026. A chart printed to one decimal place rounds by up to 0.05 psi.
The °C table is computed at whole degrees Celsius, not converted from the °F rows, and the two agree to within 0.01 psi.
Questions about the R-290 PT chart
At sea level, R-290 is at 63.9 psig at 40 °F. At 5,000 ft the same refrigerant reads 66.4 psig, because the gauge reads against thinner air.
The chart gives the saturation pressure at each temperature, not an operating target. Running pressures depend on the system, the load, the airflow and the charge. Compare with the manufacturer’s charging instructions, and use the chart to turn a gauge reading into a saturation temperature for superheat or subcooling.
When a system has been off long enough to even out, any part holding both liquid and vapor sits at the saturation pressure for its temperature. At 70 °F that is 110.2 psig for R-290 at sea level. It shows refrigerant is present, not how much.
Yes. A gauge reads against the air around it, and air pressure falls with height. At 5,000 ft the standard atmosphere is 12.23 psia instead of 14.70, so every gauge reading is about 2.5 psi higher than at sea level for the same refrigerant temperature. Set your elevation in the lookup to correct the whole chart.
R-290 is the ASHRAE refrigerant number for propane, so the pressure-temperature relationship on this page is that of propane. It is classed A3, higher flammability.
Other refrigerants
- R-22 Older US air-conditioners and heat pumpsAt 40 °F68.6 psig
- R-410A US central air-conditioners and heat pumps until 2025At 40 °F118.8 / 118.4 psig
- R-134a Car air-conditioning, since it replaced R‑12At 40 °F35.0 psig
- R-404A RefrigerationAt 40 °F86.9 / 85.4 psig
- R-454B New US air-conditioners and heat pumps since 2025At 40 °F112.0 / 107.0 psig
- R-32 New US air-conditioners and heat pumps since 2025At 40 °F121.0 psig
- R-1234yf Car air-conditioningAt 40 °F38.4 psig
- All 8 compared Every refrigerant at one temperature, and a side-by-side table from -20 to 120 °F
Pressures are gauge at sea level; for blends, liquid (bubble) / vapor (dew). Safety classes are ASHRAE 34.