  2. Data
  3. R-454B PT Chart: Pressure-Temperature Table and Lookup
Last reviewed October 2026

R-454B PT Chart

Quick Answer

At 40 °F, R-454B is at 112.0 psig as a liquid (bubble point) and 107.0 psig as a vapor (dew point), at sea level. Use the vapor value for superheat and the liquid value for subcooling.

R-454B pressure and temperature

Liquid (bubble point)112.0 psig
Vapor (dew point)107.0 psig

R-454B at 40 °F, sea level

Gauge pressure assumes sea-level air (14.7 psia). Set your elevation if you are well above sea level: a gauge reads against the air around it.

R-454B pressure-temperature chart · GreenCalculus · greencalculus.com/data/r-454b-pt-chart/

Gauge pressure at sea level, -40 to 150 °F. Use the vapor (dew) column for superheat and the liquid (bubble) column for subcooling. Below 0 psig the reading is a vacuum, in inches of mercury.

Temp (°F)Liquid, bubble (psig)Vapor, dew (psig)
-409.58.4
-3910.19.0
-3810.89.6
-3711.410.2
-3612.110.8
-3512.711.4
-3413.412.1
-3314.112.8
-3214.813.4
-3115.514.1
-3016.214.8
-2917.015.5
-2817.716.3
-2718.517.0
-2619.317.7
-2520.118.5
-2420.919.3
-2321.720.1
-2222.620.9
-2123.421.7
-2024.322.6
-1925.223.4
-1826.124.3
-1727.025.2
-1628.026.1
-1528.927.0
-1429.927.9
-1330.928.8
-1231.929.8
-1132.930.8
-1033.931.8
-935.032.8
-836.133.8
-737.134.9
-638.235.9
-539.437.0
-440.538.1
-341.739.2
-242.940.4
-144.141.5
045.342.7
146.543.9
247.845.1
349.046.3
450.347.6
551.748.8
653.050.1
754.351.4
855.752.7
957.154.1
1058.555.4
1160.056.8
1261.458.2
1362.959.7
1464.461.1
1566.062.6
1667.564.1
1769.165.6
1870.767.1
1972.368.7
2073.970.3
2175.671.9
2277.373.5
2379.075.2
2480.776.8
2582.578.5
2684.380.3
2786.182.0
2887.983.8
2989.885.6
3091.787.4
3193.689.2
3295.591.1
3397.593.0
3499.594.9
35101.596.9
36103.598.8
37105.6100.8
38107.7102.9
39109.8104.9
40112.0107.0
41114.1109.1
42116.4111.2
43118.6113.4
44120.9115.6
45123.1117.8
46125.5120.0
47127.8122.3
48130.2124.6
49132.6127.0
50135.0129.3
51137.5131.7
52140.0134.1
53142.5136.6
54145.1139.1
55147.7141.6
56150.3144.1
57153.0146.7
58155.7149.3
59158.4151.9
60161.1154.6
61163.9157.3
62166.7160.1
63169.6162.8
64172.5165.6
65175.4168.5
66178.3171.3
67181.3174.2
68184.4177.2
69187.4180.1
70190.5183.1
71193.6186.2
72196.8189.3
73200.0192.4
74203.2195.5
75206.5198.7
76209.8201.9
77213.1205.2
78216.5208.5
79219.9211.8
80223.4215.2
81226.9218.6
82230.4222.0
83234.0225.5
84237.6229.0
85241.2232.6
86244.9236.2
87248.6239.8
88252.4243.5
89256.2247.2
90260.0251.0
91263.9254.8
92267.9258.6
93271.8262.5
94275.8266.4
95279.9270.4
96284.0274.4
97288.1278.4
98292.3282.5
99296.5286.7
100300.8290.9
101305.1295.1
102309.4299.4
103313.8303.7
104318.3308.0
105322.8312.5
106327.3316.9
107331.9321.4
108336.5326.0
109341.2330.6
110345.9335.2
111350.6339.9
112355.4344.6
113360.3349.4
114365.2354.3
115370.2359.1
116375.2364.1
117380.2369.1
118385.3374.1
119390.5379.2
120395.7384.3
121400.9389.5
122406.2394.8
123411.6400.1
124417.0405.4
125422.4410.8
126427.9416.3
127433.5421.8
128439.1427.4
129444.8433.0
130450.5438.7
131456.3444.5
132462.1450.3
133468.0456.1
134473.9462.0
135479.9468.0
136485.9474.1
137492.1480.2
138498.2486.3
139504.4492.6
140510.7498.8
141517.1505.2
142523.5511.6
143529.9518.1
144536.4524.6
145543.0531.3
146549.6538.0
147556.3544.7
148563.1551.5
149569.9558.4
150576.8565.4
SourceChemours (NIST REFPROP 10)
Range-40 to 150 °F, -40 to 65 °C
Checked againstArkema, Daikin
LicenceChemours values; see Sources

R-454B is one of the two main replacements for R-410A in new US air-conditioners and heat pumps, required since 2025. This chart gives its liquid and vapor pressures at every whole degree from -40 to 150 °F, from Chemours’ published tables.

Charts disagree

Published R-454B charts disagree. Daikin’s chart reads 1.3 psi higher at 40 °F, a 0.6 °F (0.3 °C) difference; 2.8 psi higher at 100 °F, a 0.7 °F (0.4 °C) difference; and up to 4.6 psi at 150 °F. Arkema’s chart agrees with this chart to within 0.06 psi. Daikin's chart (values from Weitron) uses a different R-454B mixture model from NIST REFPROP 10; it reads higher than Chemours and Arkema, increasingly so at high temperatures. How we checked

How to read an R-454B PT chart

A pressure-temperature (PT) chart gives the pressure at which a refrigerant boils or condenses at each temperature: its saturation pressure. Where liquid and vapor are both present, as in an evaporator, a condenser or a cylinder, the pressure and the temperature are tied together, so a gauge reading tells you the temperature the refrigerant is boiling or condensing at.

R-454B is a blend, and a blend boils over a range of temperatures rather than at one. So the chart has two columns. The liquid (bubble point) pressure is where the first bubble of vapor forms; the vapor (dew point) pressure is where the last drop of liquid boils away. At the same pressure, the two temperatures differ by 2.3 °F for R-454B (the temperature glide, at the 40 °F dew-point pressure).

The pressures are gauge pressure (psig) at sea level. Below 0 psig the refrigerant is under vacuum, and the chart shows inches of mercury instead. Switch the units above to °C, kPa or bar, and type any temperature or pressure into the lookup for a value between the rows.

Superheat and subcooling: a worked example

The lookup above does both calculations. Here is what it does, with example readings. They show the method only; they are not target pressures for any system.

Worked example

Superheat. The suction gauge reads 107 psig and the suction line is at 52 °F. On the vapor (dew point) line, 107 psig is a saturation temperature of 40.0 °F. Superheat is 52 − 40.0 = 12.0 °F.

Subcooling. The liquid line gauge reads 301 psig and the liquid line is at 90 °F. On the liquid (bubble point) line, 301 psig is 100.1 °F. Subcooling is 100.1 − 90 = 10.1 °F.

Whether a superheat or subcooling figure is right for a system depends on that system. Compare with the manufacturer’s charging instructions.

How far off a reading can be

Superheat and subcooling are differences of a few degrees, so a small error in the pressure shows up in the answer. This table works out, from the R-454B chart itself, how far each common mistake moves the result.

MistakeSuperheat
suction at 40 °F
Subcooling
liquid at 100 °F
The gauge reads 1 psi offoff by 0.5 °F (0.3 °C)off by 0.2 °F (0.1 °C)
At 5,000 ft, using a sea-level chartreads high by 1.2 °F (0.7 °C)reads low by 0.6 °F (0.3 °C)
Wrong column: liquid for superheat, vapor for subcoolingreads high by 2.3 °F (1.3 °C)reads high by 2.3 °F (1.3 °C)

Worked out from this chart. For R-454B, 1 °F is about 2.1 psi at a 40 °F suction and 4.3 psi at a 100 °F liquid line. At 5,000 ft a gauge reads 2.5 psi lower than at sea level for the same refrigerant pressure.

Gauge pressure and elevation

A gauge reads the difference between the refrigerant’s pressure and the air around it. Air pressure falls with height, so at the same temperature a gauge reads higher up a mountain than at sea level. At 40 °F, R-454B vapor reads 107.0 psig at sea level and 109.5 psig at 5,000 ft, where standard air pressure is 12.23 psia.

Enter your elevation in the lookup and the whole chart, CSV and printout switch to it. The tool uses the standard atmosphere, the same basis as Arkema’s published 5,000 ft chart. Weather moves air pressure too, by much less.

About R-454B

GreenCalculus MasterBrain data version 2026.284 · 1 factor from IPCC AR6 · key refrigerants.r_454b · each resolves at verify.greencalculus.com/‹key› with its source cell.
TypeHFC/HFO blend
CompositionBlend: R-32 68.9% and R-1234yf 31.1% by mass
ASHRAE 34 safety classA2L: lower toxicity, lower flammability
GWP-100 (IPCC AR6)531
Boiling point at 1 atm (bubble)
-58.9 °F (-50.5 °C)
Critical temperature
172.6 °F (78.1 °C)
Critical pressure
763.9 psia (5,267 kPa)
Temperature glide
2.3 °F at the 40 °F dew-point pressure

Boiling point and critical point are as printed by Chemours; the glide is computed from the chart data. GWP is from our refrigerant GWP dataset; the refrigerant leakage calculator turns a leak into CO2e.

Since 1 January 2025, new US residential and light-commercial air-conditioners and heat pumps must use a refrigerant with a global warming potential below 700. R-454B is one of the two main refrigerants used to meet it, with R-32. Our R-410A, R-32 and R-454B section gives the dates and the rules they come from.

How we checked these numbers

The R-454B values are Chemours’ published table for Opteon XL41, computed with NIST REFPROP 10, converted to gauge pressure. We use it rather than our own calculation because CoolProp’s R-32/R-1234yf mixture model reads about 1% high against it (1.2 psi at 40 °F). We then compared the result with Arkema’s and Daikin’s charts:

The R-454B table is this source (copied, so the gap is zero by construction).

Daikin's chart (values from Weitron) uses a different R-454B mixture model from NIST REFPROP 10; it reads higher than Chemours and Arkema, increasingly so at high temperatures.

Checked 28 Oct 2026. A chart printed to one decimal place rounds by up to 0.05 psi.

We show the Chemours values and report the Daikin gap rather than averaging the two.

The °C table is computed at whole degrees Celsius, not converted from the °F rows, and the two agree to within 0.01 psi.

Questions about the R-454B PT chart

At sea level, R-454B is at 112.0 psig as a liquid (bubble point) and 107.0 psig as a vapor (dew point) at 40 °F. At 5,000 ft the vapor figure reads 109.5 psig.

The chart gives the saturation pressure at each temperature, not an operating target. Running pressures depend on the system, the load, the airflow and the charge. Compare with the manufacturer’s charging instructions, and use the chart to turn a gauge reading into a saturation temperature for superheat or subcooling.

When a system has been off long enough to even out, any part holding both liquid and vapor sits near the saturation pressure for its temperature. At 70 °F that is about 190.5 psig for R-454B at sea level, close to the liquid (bubble point) figure. It shows refrigerant is present, not how much.

Yes. A gauge reads against the air around it, and air pressure falls with height. At 5,000 ft the standard atmosphere is 12.23 psia instead of 14.70, so every gauge reading is about 2.5 psi higher than at sea level for the same refrigerant temperature. Set your elevation in the lookup to correct the whole chart.

Different charts use different mixture models. Chemours’ and Arkema’s tables, both from NIST REFPROP 10, agree with each other to within 0.06 psi. Daikin’s 2024 chart, which takes its values from Weitron, reads higher, by up to 4.6 psi at 150 °F. This page uses the Chemours table.

No. R-454B runs at slightly lower pressures than R-410A (at 40 °F its vapor pressure is about 11 psi lower), it is classed A2L (lower flammability) where R-410A is A1, and a system is designed for one refrigerant. Use the refrigerant on the nameplate.

Other refrigerants

Pressures are gauge at sea level; for blends, liquid (bubble) / vapor (dew). Safety classes are ASHRAE 34.

Version history

  • 1.1.1 (29 October 2026): sources moved into a compact card at the end of the page, so they no longer break up the reading.
  • 1.1 (28 October 2026): new section on how far off a reading can be, worked out for this refrigerant, and a note on how closely the published charts agree.
  • 1.0.1 (28 October 2026): other refrigerants shown as cards, with each gas’s use, pressure at 40 °F, type and safety class.
  • 1.0 (28 October 2026): first published.
Scroll to Top